19. Remote-seal

     Configures the parameters for a
     remote sealed transmitter.
      -- Auto Range (closed tank):
         Automatically calculates the range
         (LRV and URV). The user must
         enter the high pressure flange
         location, specific gravity, fill fluid,
         span, flange span, and distance of
         the zero level above the lower
         flange. This function is valid when
         conformity is linear.
      -- Set LRV (Actual): When the tank
         liquid level is known, this function
         is used to shift the range (LRV-
         URV) so that the current output
         level becomes the percentage of
         output specified by the user. This
         function is valid when conformity
         is linear.
      -- Ambient Temperature
         Compensation: Compensates for
         the effects of temperature on the
         fill fluid. The user must enter the
         flange span or fill fluid type.